- Carbon dioxide:

Measurement range: 0 … 2000

Stability in typical HVAC applications: ±(15 ppm + 2 % of reading) over 5 years

Carbon dioxide sensor: CARBOCAP GM10

- Temperature:

Measurement range: 0 … +50 °C (+32 ... +122 °F)

Temperature sensor:

On P models: Pt1000 RTD Class F0.15

- Supply voltage:

18 … 35 V DC

24 V AC ±20 % 50/60 Hz

- Max. current consumption at 18 V DC: 45 mA

1 W

- Outputs: 4 … 20 mA and/or 0 … 10 V

- Passive temperature sensor: Pt1000 RTD

- IP rating: IP30

- Weight:

Plain and LED version: 114 g (4.02 oz)

Display version: 124 g (4.37 oz)