Inputs:
Thermocouple (J, K, T, E, R, S under ITS - 90).
RTD Pt-100 under DIN 43760.
4-20 mA with input impedance of 250 Ω.
1 to 5 Vdc with input impedance >10 MΩ.
Power Supply: 75 to 264 Vac 50/60 Hz or 100 to 360 Vdc (10 W nominal); 24 Vac/dc (±10 %); 12 Vdc (±10 %).
Operation Ambient: 0 to 60 °C temperature and 90 % maximum relative humidity.
Dimensions: 140 x 93 x 173 mm HxWxD.
Weight: 0.7 kg approx
Accuracy:
± 0.1 % of full scale for TC, RTD, mA, Vdc