For full functionality of this site it is necessary to enable JavaScript.
EMIN.MY
0
Product image

HK Instruments Siro-MOD-CO2-T-D Indoor Air Quality Transmitter (CO2; T)

ModelSiro-MOD-CO2-T-D
P/N304.005.015
Contact
Secure Checkout
Quality Engagement
Easy change and return
Delivery Available

Measurement ranges:

+ CO2: 0–2000 ppm / 400–2000 ppm (selectable via jumper)

+ Temperature: 0...50 °C

Communication: RS-485 Modbus (RTU)

Accuracy:

+ CO₂: ±40 ppm + 3 % of reading (typical), additional ±60 ppm for first weeks

+ Temperature: ±0.4 °C (typical at 20 °C)

Measuring elements:

+ CO2: Non-dispersive infrared (NDIR)

+ Temperature: Integrated to CMOS

Measuring units:

+ CO2: ppm

+ Temperature: °C

Calibration (CO2): Automatic self-calibration, ABC LogicTM

Supply voltage: 24 VDC/VAC ±10 %

Output signal 1–4: 0...10 V (optional 2...10 V / 0...5 V, display or configuration tool required); Optional 4...20 mA

Linear to selected measurement (CO2, VOC, PM, rH or Temp)

Operating temperature: 0...50 °C

Protection standard: IP20

Noted:

CO2 = Carbon dioxide sensor

T = Temperature sensor

D = Display

Summary


Datasheet


Manual

Stay Updated with Offers

Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.

By subscribing, you agree to our Terms of Service and Privacy Policy.

Quick Support

Direct access to our certified experts