Measurement ranges:

+ CO2: 0–2000 ppm / 400–2000 ppm (selectable via jumper)

Communication: RS-485 Modbus (RTU)

Accuracy:

+ CO₂: ±40 ppm + 3 % of reading (typical), additional ±60 ppm for first weeks

Measuring elements:

+ CO2: Non-dispersive infrared (NDIR)

Measuring units:

+ CO2: ppm

Calibration (CO2): Automatic self-calibration, ABC LogicTM

Supply voltage: 24 VDC/VAC ±10 %

Output signal 1–4: 0...10 V (optional 2...10 V / 0...5 V, display or configuration tool required); Optional 4...20 mA

Linear to selected measurement (CO2, VOC, PM, rH or Temp)

Operating temperature: 0...50 °C

Protection standard: IP20

Noted:

CO2 = Carbon dioxide sensor

A = mA output

D = Display