Measurement ranges:

+ CO2: 400–2000 ppm

+ Temperature: 0...50 °C

Accuracy:

+ CO2: ±40 ppm + 3 % of reading, typical; DC model: 75 ppm or 10 % of reading (whichever is greater)

+ Temperature: <0.5 °C

+ Total error band includes accuracy, hysteresis and temperature effect over 5...50 °C and 10–90 % rH

Measurement elements: Temperature sensor: Pt1000 / Integrated (models with rH-measurement), Non Dispersive Infrared (NDIR) CO2 sensor, thermoset polymer capacitive sensing element for humidity

Measuring units: ppm, °C, % rH

Calibration: Automatic self-calibration, ABC LogicTM or continuous comparison (DC)

Supply voltage: 24 VDC/VAC ±10 %

Output signal 1: 0/2…10 V or 4…20 mA (linear to CO2) (2–10 V output: display required)

Optional output signal 2: 0/2…10 V or 4…20 mA (linear to rH) (2–10 V output: display required)

Output signal 3: 0/2…10 V or 4…20 mA (linear to Temp) (2–10 V output: display required)

Optional relay output: Potential free SPDT 250 VAC, 6 A / 30 VDC, 6 A with adjustable switching point and hysteresis

Operating temperature: 0...50°C

Protection standard: IP20

With dual channel sensor & display