FLUKE FLUKE-1625-2 KIT Earth Ground Testers KIT (3 poles, 4 poles)

ModelFLUKE-1625-2 KIT
P/N4325181
OriginRomania
Warranty12 months
Contact
Secure Checkout
Quality Engagement
Easy change and return
Delivery Available

-Measurement of Interference Voltage DC + AC (UST):

Measuring limits of error: method Full wave rectification

Measuring range: 1 V to 50 V

Frequency rangeDC/AC: 45 Hz to 400 Hz sine

Accuracy: ±(5% of rdg + 5 digit)

Measuring sequence: Approx. 4 measurements/s

Internal resistance: Approx. 1.5 MΩ

Max. overload: Urms = 250 V

-Measurement of Interference Frequency (F):

Measuring limits of error: method: Measurement of oscillation period of the interference voltage

Measuring range6.0 Hz to 400 Hz

Display range16.0 Hz to 299.9 Hz to 999 Hz

Resolution0.1 Hz to 1 Hz

Range1 V to 50 V

Accuracy±(1% of rdg + 2 digit)

-Earthing Resistance (RE):

Measuring methodCurrent and voltage measurement with probe as IEC61557-5

Open circuit voltage20/48 V, AC

Short circuit current250 mA AC

Measuring frequency94, 105, 111, 128 Hz selected manually or automatic. (AFC) 55 Hz in function R1

Noise rejection120 dB (16 2/3 , 50 , 60, 400 Hz)

Max. overloadUrms = 250 V

-Electrical Measurement Specifications:

Measuring range0.020 Ω to 300 kΩ

Accuracy±(2% of rdg + 2 digit)

Operating error±(5% of rdg + 5 digit)

-Automatic Switchover of Measuring Resolution in Dependence to Auxiliary Earth Electrode Resistance RH:

RH with Umeas = 48 V: < 300 Ω, < 6 Ω, < 60 Ω, < 600 Ω

RH with Umeas = 20 V: < 250 Ω. < 2.5 kΩ, < 25 kΩ, < 250 kΩ

-Selective Measurement of the Earthing Resistance (RE Clamp):

Measuring range0.020 Ω to 300 kΩ

-Resistance Measurement (R~):

Measuring range0.020 Ω to 300 kΩ

-Resistance Measurement (R DC):

Measuring range0.020 Ω to 300 kΩ

-Compensation of Lead Resistance (RK):

Compensation of lead resistance (RK) can be switched on in functions RE 3-pole, RE 4-pole (clamp), R AC, and R DC 2-pole

-Stakeless Ground Loop Measurement (Two Clamp Stakeless)

Measuring range0.02 Ω to 199.9 Ω

Includes:

GEO Earth Ground Tester1625-2

User’s Manual

Batteries

Quick Reference Guide

USB Cable

2 Clamps

C1620 Professional Carrying Case

4 Earth Ground Stakes

3 Cable Reels

Datasheet


Manual 

Stay Updated with Offers

Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.

By subscribing, you agree to our Terms of Service and Privacy Policy.

Quick Support

Direct access to our certified experts