Calibration: R-12, R-123, R-125, R-134a, R-143, R-22, R-404a, R-407c, R-410a, R-507, R-514a, R-1234yf, R-1234ze etc

Default calibration:R-404a

Sensor type: metal-oxide semiconductor

Sampling method: Diffusion

Sensor lifetime: > 5 years

Power supply: 24 VDC/AC ±20% (default) or 230 VAC (optional)

Digital interface: UART

Output relays: 2 × SPST relays (switch-over contact), 250 VAC / 30 VDC, 5A max

Alarms:blinking LED, buzzer 85 dB

Default alarm set points:200 ppm / 400 ppm halocarbon gas

Enclosure: light-grey ABS plastic with ventilation slots, IP20

Dimensions: H85 × W85 × D36 mm

Operating conditions: -40...+70 °C, 0...95%RH