For full functionality of this site it is necessary to enable JavaScript.
EMIN.MY
0
Product image

ETCR ETCR3250 Pylon Earth Resistance Tester (9000kΩm, 500AAC, 200VAC)

USD 2,216.36
Secure Checkout
Quality Engagement
Easy change and return
Delivery Available

Basic Error & Performance Indicator Under Reference Condition

Measurement Function

Measuring Range/Accuracy/Resolution

Earth Resistance(R) (4 Clamp Method)

0.10Ω~20.00Ω/±10%rdg±5dgt/0.01Ω

20.0Ω~200.0Ω/±10%rdg±5dgt/0.1Ω

Earth Resistance(R)

0.10Ω~20.00Ω/±2%rdg±3dgt/0.01Ω

20.0Ω~200.0Ω/±2%rdg±3dgt/0.1Ω

200Ω~2000Ω/±2%rdg±3dgt/1Ω

2.00kΩ~20.00kΩ/±4%rdg±3dgt/10Ω

Soil Resistivity (ρ)

0.00Ωm~99.99Ωm/ (ρ=2πaRa:1m~100m; π=3.14) /0.01Ωm

100.0Ωm~999.9Ωm/ (ρ=2πaRa:1m~100m; π=3.14) /0.1Ωm

1000Ωm~9999Ωm/ (ρ=2πaRa:1m~100m; π=3.14) /1Ωm

10.00kΩm~99.99kΩm/ (ρ=2πaRa:1m~100m; π=3.14) /10Ωm

100.0kΩm~999.9kΩm/ (ρ=2πaRa:1m~100m; π=3.14) /100Ωm

1000kΩm~9000kΩm/ (ρ=2πaRa:1m~100m; π=3.14) /1kΩm

Earth Current(A~)

1.00mA~50.00mA/±2%rdg±3dgt/0.01mA

0.50A~5.000A/±2%rdg±3dgt/0.001A

5.0A~500.0A/±3%rdg±3dgt/0.1A

Earth Voltage(V~)

0.0V~200.0V/±2%rdg±3dgt/0.1V

General Specification

Power Supply: DC 7.4V 5200mAh rechargeable lithium battery, the battery is fully charged about 8.4V

Display Mode: 7 inches color LCD

Measurement Instruction: LED flash during the measurement

LCD Size: 151mm×83mm

Measurement Range

Four clamp method to measure earth resistance: 200Ω

Earth resistance: 0.00Ω~20.00kΩ

Soil resistivity: 0.00Ωm~9000kΩm

Measurement: Four clamp measurement method, Precision four, three-wire measurement method, simple two-wire measurement method to measure earth resistance, AC current, earth voltage

Measuring Method: Pylon earth resistance: Four clamp measurement method

Earth resistance: rated current pole-change method, measuring current 55mA Max

Soil resistivity: Quadrupole method(Wenner)

AC current: clamp type CT, effective value acquisition

Earth voltage: component voltage, effective value acquisition

Test Frequency: 128Hz/111Hz/105Hz/94Hz(AFC)

Short Circuit Test Current: AC 55mA max

Open Circuit Test Voltage: AC 15V max

Test Voltage Waveform: Sine wave

Electrode Spacing Range: Range can be set 1m~100m

Gear Shift

Four clamp measurement method to measure earth resistance: 200Ω fully automatic gear shift

Earth resistance: 0.00Ω~20.00kΩ fully automatic gear shift

Soil resistivity: 0.00Ωm~9000kΩm fully automatic gear shift

AC current(single CT): 1.00mA~500A fully automatic gear shift

Earth voltage: 0.0V~200.0V

Standard Test Line: 4 PCS: red 20m, black 20m, yellow 10m, green 10m each 1 PCS

Simple Test Line: 2 PCS: red 1.6m, black 1.6m each 1 PCS

Auxiliary Ground Rod: 4 PCS: φ9mm×230mm(about 935g)

Measurement Time: Earth resistance, soil resistivity: about 30 seconds/time

Line Voltage: Measurement below AC 600V

Communication Interface: With USB interface, software monitoring, storage data can be uploaded to the computer, saved and printed

Printer: Built in

Memory: 100 groups, “001/100” storage instruction,"100/100" indicates that the storage is full

Overflow Display: When over-range overflow "OL" symbol display

Auxiliary Ground Test: With auxiliary grounding resistance value test function, 0.00kΩ~20kΩ(100R+rC<20kΩ,100R+rP<20kΩ)

Alarm Function: When the measured value exceed the alarm set value, the ”siren" alarm symbol prompt

Alarm Threshold Setting Range: Resistance: 0Ω~2000Ω, voltage: 0V~200V, current: 0A~600mA

Automatic Shutdown: Start up 30 minutes without any operation, and then automatic shutdown

Battery Voltage: When the battery voltage drop to about DC 7.2V±0.1V, the low battery voltage symbol indicate to remind that the tester need to be charged.

Working Current

Standby: about 400mA

Measurement: about 550mA

Caliber Of Current Clamp: Φ68mm

Tester Size: 355mm×272mm×164mm

Weight

Tester: about 2765g(include battery)

Current clamp: about 500g×4 PCS

Total weight: about 9000g (include accessory)

Overload Protection: Measurement earth resistance: AC 280V/3 seconds between C(H)-E, P(S)-ES

Protection Level: IP65 (cover closed)

Insulation Resistance: Above 20MΩ(500V between the circuit and the housing)

Withstand Voltage: AC 3700V/rms (between circuit and housing)

Electromagnetic Characteristics: IEC61326(EMC)

Suitable Safety Standard: IEC61010-1(CAT Ⅲ 300V, CAT IV 150V, pollution level 2); IEC61010-031; IEC61557-1(earth resistance); IEC61557-5(soil resistivity);

JJG 366-2004

Working Temperature & Humidity: -10℃~40℃; below 80%rh

Storage Temperature & Humidity: -20℃~60℃; below 70%rh

Catalog

Stay Updated with Offers

Get exclusive volume discounts, bulk pricing updates, and new product alerts delivered directly to your inbox.

By subscribing, you agree to our Terms of Service and Privacy Policy.