Dwyer DHII-016 Digihelic® Differential Pressure Controller, NEMA 4, 2 Relays, Modbus (± 0.5 %, Differential, 5 NOT VALID, NPT Female, (2) SPDT)
Weight: 2.62 lb
Accuracy: ± 0.5 %
Baud Rate: 9600
Materials: Aluminum, Glass
Stability: <± 1%/year
Compliance: CE, UL
Switch Note: 8 A at 240 VAC resistive
Switch Type: (2) SPDT
Display Note: 4 digit backlit LCD 0.6˝ height. LED indicators for set point and alarm status
Display Type: LCD
Accuracy Note: ± 0.5% at 77°F (25°C) including hysteresis and repeatability (after 1 hour warm-up)
Output Detail: 4-20 mA DC into 900 Ω max
Output Signal: Current
Pressure Type: Differential
Pressure, Max: 5 NOT VALID
Pressure, Min: -5 NOT VALID
Response Time: 250 ms
Switch Rating: 8 A @ 240 Vac
Data Interface: Modbus RTU, RS485
Supply Voltage: 100 to 240 Vac/132 to 240 Vdc
Thermal Effects: 0.020%/°F @ 77°F
Number of Digits: 4
Enclosure Ratings: IP66, NEMA Type 4X
Materials, Wetted: Consult Factory
Power Consumption: 7 VA, Low Power: 130 mA
Supply Power Note: High voltage power = 100-240 VAC, 50-400 Hz or 132-240 VDC, Low voltage power = 24 VDC ± 20%.
Supply Power Type: AC/DC
Response Time Note: 250 ms (damping set to 1)
Media Compatibility: Air, Argon, Carbon dioxide, Helium, Nitrogen, Non-Corrosive Dry Gases
Mounting Orientation: Horizontal
Set Point Adjustment: Menu Configurable
Electrical Connection: 1/2 in NPT female Conduit with Screw Terminal block
Process Connection Size: 1/8 in
Process Connection Type: NPT Female
Operating Temperature, Max: 140 °F
Operating Temperature, Min: 32 °F
Compensated Temperature, Max: 140 °F
Compensated Temperature, Min: 32 °F
Zero Setting Adjustable Range: Accessible via Menus