Drift: <5%/Year in Air
Weight: 0.28 lb
Accuracy: ± 2 %, ± 5% with transitional flow
Compliance: CE
Sensor Life: 4 Years
Sensor Type: Field Replaceable Electrochemical
Display Type: N/A
Coverage Area: 5000 to 7000 sq ft
Output Detail: Jumper selectable 4-20 mA (loop powered) or 2-10 V (load must be >50 kΩ)
Output Signal: Current, Voltage
Response Time: <45 s to 90%
Enclosure Type: Rugged Housing
Supply Voltage: Current: 18 to 28 Vdc; Voltage: 18 to 28 Vdc/Vac
Gas Concentration: 0 to 200 ppm
Relative Humidity: 15 to 90% RH Constant, 0 to 99% RH Intermittent
Supply Power Note: Current output: 18-28 VDC; Voltage output: 18-28 VDC/ VAC, reverse polarity protected
Supply Power Type: AC/DC
Calibration Option: N/A
Additional Features 1: Rugged Housing
Electrical Connection: Conduit Knockouts with terminal block
Storage Temperature, Max: 68 °F
Storage Temperature, Min: 32 °F
Operating Temperature, Max: 122 °F
Operating Temperature, Min: -4 °F
Zero Setting Adjustable Range: 15 Turn Potentiometers