ELECTRICAL SPECIFICATIONS

Input

Input voltage range: 90 to 264 VAC or 127 to 350 VDC

Frequency: 47 to 63 Hz (360 to 400 Hz with higher leakage)

Inrush current: 50 Apk, cold start

Leakage current: <300 µA (using UL test method)

No load power: < 500 mW


Output

Output Voltage: 12V

Vout Adjust Range (-0% / +15%): 12-13.8V

Minimum Load: 0 A

Max. Continuous Load (Free Air): 54.2 A

Max. Peak Load (Free Air): 62.5 A

Max. Continuous Load (Forced Air): NA

Max. Peak Load (Forced Air): NA

Regulation: ±2%

Ripple (p-p): 120 mV

Maximum power: 650 W, forced-air cooling (750 W peak); 400 W, free-air natural convection cooling (650 W peak)

Adjustment range: -0% to +15%

Holdup time: 20 ms @ 400 W

Fan output: 12 V @ 1.0 A (forced air); 12 V @ 0.5 A (natural convection)

Standby output: 5 V @ 2.0 A (forced air); 5 V @ 1.0 A (natural convection)


Control and Protection

Serial bus interface: PMBus®

Current share: Active

Remote sense: 2-wire (+ and -)

Remote inhibit: Pull inhibit low = main & fan output OFF (5 V standby is ON); Pull inhibit high (or floating) = all outputs ON

AC OK: Active high when normal AC input is present (with internal 10 kOhm pull up to 3.3 V)

DC OK: Active high when main O/P is within regulation (with internal 10 kOhm pull up to 3.3 V)

Smart fan control: Monitor, control and override

Overvoltage protection: Latch (AC recyle or inhibit toggle required for PSU restart)

Overload protection: Auto-recovery (constant current mode down to 50% Vout)

Overtemperature protection: Auto-recovery with hysteresis


ENVIRONMENTAL SPECIFICATIONS

Operating temperature: -20 °C to +80 °C (derate at 50 °C), startup at -40 °C

Storage temperature: -40 °C to +85 °C

Operating humidity: 5% to 95% (non-condensing)

Non-operating humidity: 5% to 95% (non-condensing)

Maximum altitude: 5000 m (3000 m for medical), derating may apply


OTHER SPECIFICATIONS

Isolation: 4000 VAC (input to output); 1500 VAC (input to PE, output to PE)

Line harmonics: EN 61000-3-2, Class A

ESD immunity: EN 61000-4-2, ±15kV (air) / ±8kV (contact) - Criterion A

Conducted EMI Level B, CISPR 22 and FCC Part 15

Radiated EMI: Level B, CISPR 22 and FCC Part 15 (with cover)

Surge immunity: EN 61000-4-5, Level 3 - Criterion A, Level 4 - Criterion C

Medical EMC: EN 60601-1-2: 2014 (cover maybe required for some tests)

MTBF (Telcordia, Issue 3, Method 1, Case 3): > 950 KHrs, 25 °C, 410 W natural convection; > 1.3 MHrs, 25 °C, 650 W forced air